A permanently installed system that continuously monitors for refrigerant loss and alerts on it, either by sensing refrigerant in air (direct) or by inferring loss from system behavior (indirect). Direct systems must detect at 10 ppm and alert at 100 ppm; indirect systems must alert at a loss of 50 pounds or 10% of full charge, whichever is less.