The Refrigerant Compliance Glossary

A leak rate, a full charge, a 15-pound threshold. The terms that trigger deadlines, reports, and penalties, defined in plain language.
Filter by Definition Types

Exceedance

The event of an appliance’s calculated leak rate crossing its regulatory threshold. It starts every downstream clock — repair, verification, follow-up verification, and, if repair fails, a retrofit or retirement plan.

Compliance Concepts & Calculations

Rolling Average Method

A leak-rate calculation that sums all refrigerant added over the prior 365 days — or since the last successful follow-up verification test — and divides by full charge. It is the method most equipment owners choose.

Compliance Concepts & Calculations

Annualizing Method

A leak-rate calculation that projects a single refrigerant addition across a full year, dividing the amount added by full charge and scaling by the days elapsed since the previous addition, capped at 365. It answers “if this loss rate continued for a year, how much would we lose?”

Compliance Concepts & Calculations

Leak Rate Threshold

The leak-rate percentage that triggers mandatory repair, set by regulatory class: 10% for comfort cooling and most other equipment, 20% for commercial refrigeration, and 30% for industrial process refrigeration under federal rules. Washington uses stricter figures of 8%, 16%, and 24%.

Compliance Concepts & Calculations

Leak Rate (Leak Loss Rate / LLR)

The percentage of an appliance’s full charge lost over a year, calculated from the refrigerant added to it. EPA permits two methods — annualizing and rolling average — and requires the same method for every appliance at a facility.

Compliance Concepts & Calculations

Nameplate Charge

The refrigerant quantity printed on the equipment data plate by the manufacturer. It is a common starting point for establishing full charge but is not automatically the same number.

Compliance Concepts & Calculations

Full Charge

The amount of refrigerant an appliance holds when it is operating normally with all components at their designed capacity. EPA accepts four ways to establish it: the manufacturer’s determination, calculation from component and piping volumes, actual measurement of refrigerant added and evacuated, or a documented range using its midpoint.

Compliance Concepts & Calculations